RFC1628 - UPS Management Information Base(2)

时间:2005-02-14 来源: 作者: 点击:
different manufacturer-selected values must be supported." ::= { upsCompliances 3 } -- -- units of conformance -- -- summary at a glance: -- subset basic adv --upsIdentManufacturer x x x --upsIdentMo
  
different manufacturer-selected values must be
supported."

::= { upsCompliances 3 }

--
-- units of conformance
--

-- summary at a glance:

-- subset basic adv
--upsIdentManufacturer x x x
--upsIdentModel x x x

--upsIdentUPSSoftwareVersion x x
--upsIdentAgentSoftwareVersion x x x
--upsIdentName x x x
--upsIdentAttachedDevices x x
--
--upsBatteryStatus x x x notes
--upsSecondsOnBattery x x x
--upsEstimatedMinutesRemaining x
--upsEstimatedChargeRemaining x
--upsBatteryVoltage
--upsBatteryCurrent
--upsBatteryTemperature
--
--upsInputLineBads x x x
--upsInputNumLines x x
--upsInputFrequency x x
--upsInputVoltage x x
--upsInputCurrent
--upsInputTruePower
--
--upsOutputSource x x x notes
--upsOutputFrequency x x
--upsOutputNumLines x x
--upsOutputVoltage x x
--upsOutputCurrent x
--upsOutputPower x
--upsOutputPercentLoad x
--
--
--upsBypassFrequency x x notes
--upsBypassNumLines x x
--upsBypassVoltage x x
--upsBypassCurrent
--upsBypassPower
--
--
--upsAlarmsPresent x x x
--upsAlarmDescr x x x notes
--upsAlarmTime x x x
--
--upsTestId x x notes
--upsTestSpinLock x x
--upsTestResultsSummary x x
--upsTestResultsDetail x x
--upsTestStartTime x x
--upsTestElapsedTime x x
--
--upsShutdownType x x x notes

--upsShutdownAfterDelay x x x
--upsStartupAfterDelay x x
--upsRebootWithDuration x x
--upsAutoRestart x x x notes
--
--upsConfigInputVoltage x x x notes
--upsConfigInputFreq x x x notes
--upsConfigOutputVoltage x x x notes
--upsConfigOutputFreq x x x notes
--upsConfigOutputVA x x x
--upsConfigOutputPower x x x
--upsConfigLowBattTime x x notes
--upsConfigAudibleStatus x x
--upsConfigLowVoltageTransferPoint
--upsConfigHighVoltageTransferPoint

-- units of conformance
upsGroups OBJECT IDENTIFIER ::= { upsConformance 2 }

upsSubsetGroups OBJECT IDENTIFIER ::= { upsGroups 1 }

upsSubsetIdentGroup OBJECT-GROUP
OBJECTS { upsIdentManufacturer, upsIdentModel,
upsIdentAgentSoftwareVersion, upsIdentName,
upsIdentAttachedDevices }
STATUS current
DESCRIPTION
"The upsSubsetIdentGroup defines objects which are
common across all UPSs which meet subset compliance.
Most devices which conform to the upsSubsetIdentGroup
will provide access to these objects via a proxy
agent. If the proxy agent is compatible with multiple
UPS types, configuration of the proxy agent will
require specifying some of these values, either
individually, or as a group (perhaps through a table
lookup mechanism based on the UPS model number)."
::= { upsSubsetGroups 1 }

upsSubsetBatteryGroup OBJECT-GROUP
OBJECTS { upsBatteryStatus, upsSecondsOnBattery }
STATUS current
DESCRIPTION
"The upsSubsetBatteryGroup defines the objects that
are common to battery groups of two-contact UPSs."
::= { upsSubsetGroups 2 }

upsSubsetInputGroup OBJECT-GROUP

OBJECTS { upsInputLineBads }
STATUS current
DESCRIPTION
"The upsSubsetInputGroup defines the objects that are
common to the Input groups of two-contact UPSs."
::= { upsSubsetGroups 3 }

upsSubsetOutputGroup OBJECT-GROUP
OBJECTS { upsOutputSource }
STATUS current
DESCRIPTION
"The upsSubsetOutputGroup defines the objects that are
common to the Output groups of two-contact UPSs."
::= { upsSubsetGroups 4 }

-- { upsSubsetGroups 5 } is reserved for
-- future use (upsSubsetBypassGroup)

upsSubsetAlarmGroup OBJECT-GROUP
OBJECTS { upsAlarmsPresent, upsAlarmDescr, upsAlarmTime }
STATUS current
DESCRIPTION
"The upsSubsetAlarmGroup defines the objects that are
common to the Alarm groups of two-contact UPSs."
::= { upsSubsetGroups 6 }

-- { upsSubsetGroups 7 } is reserved for
-- future use (upsSubsetTestGroup)

upsSubsetControlGroup OBJECT-GROUP
OBJECTS { upsShutdownType, upsShutdownAfterDelay,
upsAutoRestart }
STATUS current
DESCRIPTION
"The upsSubsetControlGroup defines the objects that
are common to the Control groups of two-contact UPSs."
::= { upsSubsetGroups 8 }

upsSubsetConfigGroup OBJECT-GROUP
OBJECTS { upsConfigInputVoltage, upsConfigInputFreq,
upsConfigOutputVoltage, upsConfigOutputFreq,
upsConfigOutputVA, upsConfigOutputPower }
STATUS current
DESCRIPTION
"The upsSubsetConfigGroup defines the objects that are
common to the Config groups of two-contact UPSs."
::= { upsSubsetGroups 9 }

upsBasicGroups OBJECT IDENTIFIER ::= { upsGroups 2 }

upsBasicIdentGroup OBJECT-GROUP
OBJECTS { upsIdentManufacturer, upsIdentModel,
upsIdentUPSSoftwareVersion,
upsIdentAgentSoftwareVersion, upsIdentName }
STATUS current
DESCRIPTION
"The upsBasicIdentGroup defines objects which are
common to the Ident group of compliant UPSs which
support basic functions."
::= { upsBasicGroups 1 }

upsBasicBatteryGroup OBJECT-GROUP
OBJECTS { upsBatteryStatus, upsSecondsOnBattery }
STATUS current
DESCRIPTION
"The upsBasicBatteryGroup defines the objects that are
common to the battery groups of compliant UPSs which
support basic functions."
::= { upsBasicGroups 2 }

upsBasicInputGroup OBJECT-GROUP
OBJECTS { upsInputLineBads, upsInputNumLines,
upsInputFrequency, upsInputVoltage }
STATUS current
DESCRIPTION
"The upsBasicInputGroup defines the objects that are
common to the Input groups of compliant UPSs which
support basic functions."
::= { upsBasicGroups 3 }

upsBasicOutputGroup OBJECT-GROUP
OBJECTS { upsOutputSource, upsOutputFrequency,
upsOutputNumLines, upsOutputVoltage }
STATUS current
DESCRIPTION
"The upsBasicOutputGroup defines the objects that are
common to the Output groups of compliant UPSs which
support basic functions."
::= { upsBasicGroups 4 }

upsBasicBypassGroup OBJECT-GROUP
OBJECTS { upsBypassFrequency, upsBypassNumLines,
upsBypassVoltage }
STATUS current
DESCRIPTION
"The upsBasicBypassGroup defines the objects that are

common to the Bypass groups of compliant UPSs which
support basic functions."
::= { upsBasicGroups 5 }

upsBasicAlarmGroup OBJECT-GROUP
OBJECTS { upsAlarmsPresent, upsAlarmDescr, upsAlarmTime }
STATUS current
DESCRIPTION

"The upsBasicAlarmGroup defines the objects that are
common to the Alarm groups of compliant UPSs which
support basic functions."
::= { upsBasicGroups 6 }

upsBasicTestGroup OBJECT-GROUP
OBJECTS { upsTestId, upsTestSpinLock,
upsTestResultsSummary, upsTestResultsDetail,
upsTestStartTime, upsTestElapsedTime }
STATUS current
DESCRIPTION
"The upsBasicTestGroup defines the objects that are
common to the Test groups of compliant UPSs which
support basic functions."
::= { upsBasicGroups 7 }

upsBasicControlGroup OBJECT-GROUP
OBJECTS { upsShutdownType, upsShutdownAfterDelay,
upsStartupAfterDelay, upsRebootWithDuration,
upsAutoRestart }
STATUS current
DESCRIPTION
"The upsBasicControlGroup defines the objects that are
common to the Control groups of compliant UPSs which
support basic functions."
::= { upsBasicGroups 8 }

upsBasicConfigGroup OBJECT-GROUP
OBJECTS { upsConfigInputVoltage, upsConfigInputFreq,
upsConfigOutputVoltage, upsConfigOutputFreq,
upsConfigOutputVA, upsConfigOutputPower,
upsConfigLowBattTime, upsConfigAudibleStatus }
STATUS current
DESCRIPTION
"The upsBasicConfigGroup defines the objects that are
common to the Config groups of UPSs which support
basic functions."
::= { upsBasicGroups 9 }

upsFullGroups OBJECT IDENTIFIER ::= { upsGroups 3 }

upsFullIdentGroup OBJECT-GROUP
OBJECTS { upsIdentManufacturer, upsIdentModel,
upsIdentUPSSoftwareVersion,
upsIdentAgentSoftwareVersion, upsIdentName,
upsIdentAttachedDevices }
STATUS current
DESCRIPTION
"The upsFullIdentGroup defines objects which are
common to the Ident group of fully compliant UPSs."
::= { upsFullGroups 1 }

upsFullBatteryGroup OBJECT-GROUP
OBJECTS { upsBatteryStatus, upsSecondsOnBattery,
upsEstimatedMinutesRemaining,
upsEstimatedChargeRemaining }
STATUS current
DESCRIPTION
"The upsFullBatteryGroup defines the objects that are
common to the battery groups of fully compliant UPSs."
::= { upsFullGroups 2 }

upsFullInputGroup OBJECT-GROUP
OBJECTS { upsInputLineBads, upsInputNumLines,
upsInputFrequency, upsInputVoltage }
STATUS current
DESCRIPTION
"The upsFullInputGroup defines the objects that are
common to the Input groups of fully compliant UPSs."
::= { upsFullGroups 3 }

upsFullOutputGroup OBJECT-GROUP
OBJECTS { upsOutputSource, upsOutputFrequency,
upsOutputNumLines, upsOutputVoltage,
upsOutputCurrent, upsOutputPower,
upsOutputPercentLoad }
STATUS current
DESCRIPTION
"The upsFullOutputGroup defines the objects that are
common to the Output groups of fully compliant UPSs."
::= { upsFullGroups 4 }

upsFullBypassGroup OBJECT-GROUP
OBJECTS { upsBypassFrequency, upsBypassNumLines,
upsBypassVoltage }
STATUS current
DESCRIPTION

"The upsFullBypassGroup defines the objects that are
common to the Bypass groups of fully compliant UPSs."
::= { upsFullGroups 5 }

upsFullAlarmGroup OBJECT-GROUP
OBJECTS { upsAlarmsPresent, upsAlarmDescr, upsAlarmTime }
STATUS current
DESCRIPTION

"The upsFullAlarmGroup defines the objects that are
common to the Alarm groups of fully compliant UPSs."
::= { upsFullGroups 6 }

upsFullTestGroup OBJECT-GROUP
OBJECTS { upsTestId, upsTestSpinLock,
upsTestResultsSummary, upsTestResultsDetail,
upsTestStartTime, upsTestElapsedTime }
STATUS current
DESCRIPTION
"The upsFullTestGroup defines the objects that are
common to the Test groups of fully compliant UPSs."
::= { upsFullGroups 7 }

upsFullControlGroup OBJECT-GROUP
OBJECTS { upsShutdownType, upsShutdownAfterDelay,
upsStartupAfterDelay, upsRebootWithDuration,
upsAutoRestart }
STATUS current
DESCRIPTION
"The upsFullControlGroup defines the objects that are
common to the Control groups of fully compliant UPSs."
::= { upsFullGroups 8 }

upsFullConfigGroup OBJECT-GROUP
OBJECTS { upsConfigInputVoltage, upsConfigInputFreq,
upsConfigOutputVoltage, upsConfigOutputFreq,
upsConfigOutputVA, upsConfigOutputPower,
upsConfigLowBattTime, upsConfigAudibleStatus }
STATUS current
DESCRIPTION
"The upsFullConfigGroup defines the objects that are
common to the Config groups of fully compliant UPSs."
::= { upsFullGroups 9 }

END

5. Acknowledgements

The UPS MIB represents the combined work of the IETF UPS MIB Working
Group, with particular, substantial authorship contributions from:

Mike Davison
Fibercom, Inc.

Ray Wasson
Consultant

Roger Draper
Liebert Corporation

Ken Key
SNMP Research, Incorporated

Pete Yoest
American Power Conversion

Doug Rademacher
American Power Conversion

Ron Pitt
Network Security Systems, Inc

Terry Zumwalt
International Power Machines

Lawren Markle
Tripp Lite

Bill Elliot
ONEAC

Tom Brennan
Exide Electronics

Brian Young
Best Power Technology

6. References

[1] Case, J., Fedor, M., Schoffstall, M., and J. Davin, "Simple
Network Management Protocol", STD 15, RFC1157, SNMP Research,
Inc., Performance Systems International, Performance Systems
International, MIT Laboratory for Computer Science, May 1990.

[2] Case, J., McCloghrie, K., Rose, M., and S. Waldbusser, "Protocol
Operations for Version 2 of the Simple Network Management
Protocol (SNMPv2)", RFC1448, SNMP Research, Inc., Hughes LAN
Systems, Dover Beach Consulting, Inc., Carnegie Mellon
University, April 1993.

[3] McCloghrie, K., and M. Rose, Editors, "Management Information
Base for Network Management of TCP/IP-based internets: MIB-II",
STD 17, RFC1213, Hughes LAN Systems, Performance Systems
International, March 1991.

[4] Case, J., McCloghrie, K., Rose, M., and S. Waldbusser, "Structure
of Management Information for Version 2 of the Simple Network
Management Protocol (SNMPv2)", RFC1442, SNMP Research, Inc.,
Hughes LAN Systems, Dover Beach Consulting, Inc., Carnegie Mellon
University, April 1993.

[5] Case, J., McCloghrie, K., Rose, M., and S. Waldbusser,
"Conformance Statements for Version 2 of the Simple Network
Management Protocol (SNMPv2)", RFC1444, SNMP Research, Inc.,
Hughes LAN Systems, Dover Beach Consulting, Inc., Carnegie Mellon
University, April, 1993.

[6] Case, J., McCloghrie, K., Rose, M., and S. Waldbusser, "Textual
Conventions for Version 2 of the Simple Network Management
Protocol (SNMPv2)", RFC1443, SNMP Research, Inc., Hughes LAN
Systems, Dover Beach Consulting, Inc., Carnegie Mellon
University, April 1993.

7. Security Considerations

Security issues are not discussed in this memo.

8. Author's Address

Jeffrey D. Case, Ph.D.
SNMP Research, Incorporated
3001 Kimberlin Heights Road
Knoxville, Tennessee 37920

Phone: (615) 573-1434